CHBEB 2000 kVA dry-type transformer provides high-capacity power distribution for hyperscale data centers and critical industrial facilities, with additional capacity that can improve operating efficiency under heavy loads. When supplying a 1600 kVA load, it operates at 80% of its rated capacity, reducing current and copper losses compared with a 1600 kVA transformer operating at full load. This lower loss level also reduces heat generation and thermal stress on winding insulation, helping extend insulation service life and support long-term operational reliability.

2,000 kVA Dry-Type Transformer Awaiting Testing
Technical Specifications
|
Parameter |
Standard Specification |
|
Product Name |
2000 kVA Dry-Type Transformer |
|
Transformer Type |
Three-Phase Cast-Resin Dry-Type Distribution Transformer |
|
Rated Capacity |
2000 kVA |
|
Number of Phases |
Three-phase |
|
Rated Frequency |
50 Hz |
|
Rated Primary Voltage |
11 kV |
|
Rated Secondary Voltage |
0.415 kV |
|
HV Tapping Range |
±2 × 2.5%, 5 positions |
|
Tap-Changing Method |
De-energized tap changing |
|
Vector Group |
Dyn11 |
|
Short-Circuit Impedance |
6.0% |
|
No-Load Current |
≤0.9% |
|
Cooling Method |
AN, air-natural |
|
Insulation Construction |
Vacuum-cast epoxy-resin insulation with fully encapsulated HV windings |
|
Winding Material |
Copper |
|
Core Material |
Cold-rolled grain-oriented silicon steel |
|
Thermal Insulation Class |
Class F |
|
Winding Temperature Rise |
100 K |
|
Partial Discharge Level |
≤10 pC |
|
Environmental / Climatic / Fire Class |
E2, C2, F1 |
|
Enclosure Protection Degree |
IP23 |
|
Temperature Monitoring |
PT100 sensors, digital temperature controller, alarm and trip contacts |
|
Installation |
Indoor installation, continuous duty |
|
Service Conditions |
Maximum ambient temperature: 40°C; maximum altitude: 1,000 m |
|
Certification Standards |
Available according to IEC, IEEE/ANSI, UL, CSA, DOE (where applicable), CE/EN, UKCA, GOST/EAC, SASO/SABER, SONCAP, ISO, and other required certification schemes |
Advantages of CHBEB 2000 kVA Dry Type Transformer
CHBEB 2000 kVA dry type transformers are engineered for high-capacity power distribution, with specialized winding, shielding, and connection designs to support reliable electrical performance.
K-Factor Harmonic Mitigation
Available with K-13 or K-20 ratings, the transformer is designed to handle harmonic currents generated by nonlinear loads. A 200%-rated neutral conductor and foil windings help accommodate elevated neutral currents and reduce skin-effect losses, limiting additional heating and thermal stress on the winding system.
Electrostatic Noise Shielding
The transformer incorporates a grounded copper screen between the primary and secondary windings to intercept electrical noise transferred through capacitive coupling and direct it to ground. This shielding helps reduce high-frequency interference between windings, supporting cleaner power delivery to downstream electrical equipment.
Bus Duct Flange Interface
With a rated secondary current of approximately 2,887 A at 400V, the transformer requires a connection system designed for high-current distribution. A precision-engineered enclosure flange enables direct integration with copper busbar trunking, while braided copper flexible links accommodate mechanical movement and help reduce stress on terminal connections.



Typical Application Context
- Tier 3/4 Data Centers
- Semiconductor Manufacturing Plants
- High-Rise Chiller Systems
- Hyperscale Computing Facilities
- Large Commercial Complexes
- Industrial Manufacturing Plants
- Critical Power Distribution Systems
- HVAC and Building Utility Systems
2000 kVA dry type transformer powering Tier 4 data center server
racks.
Customize 2000 kVA Dry Type Transformer for Your Power Distribution Project
CHBEB provides configurable electrical, winding, cooling, protection, and documentation options to match project-specific power distribution requirements.
- Electrical Ratings - Customize primary and secondary voltage, frequency, impedance, vector group, and tap configuration according to project requirements.
- Winding & Core Materials - Select copper or aluminum windings and suitable core materials according to required electrical performance and operating conditions.
- Cooling Configuration - Configure natural air or forced-air cooling according to the required load capacity, installation conditions, and operating requirements.
- Insulation & Protection - Configure cast-resin insulation, temperature monitoring, enclosure protection, and other electrical protection requirements for the intended installation environment.
- Dimensions & Installation - Customize overall dimensions, terminal arrangements, enclosure configuration, and other structural details to suit available installation space and system connections.
- Testing & Documentation - Provide project-specific testing, technical drawings, nameplate information, and inspection documents according to customer or project requirements.

Quality Assurance & Testing by CHBEB for Transformer Manufacturing
CHBEB applies quality controls throughout material inspection, production, and final testing to maintain consistent performance and reliability for dry type transformers.
Incoming Material Inspection
Inspect silicon steel core materials, winding conductors, cast-resin insulation materials, and other key components before production. Material properties are verified against applicable GB/T and IEC requirements to ensure consistent input quality.
01
Production Process Control
Monitor core lamination, winding dimensions, insulation application, and cast-resin curing throughout manufacturing. Key process controls help maintain dimensional accuracy, insulation integrity, and consistent winding quality for dry type transformers.
02
In-Factory Quality Testing
Perform voltage ratio, winding resistance, load and no-load loss, impedance voltage, insulation resistance, withstand voltage, and partial discharge tests according to applicable IEC 60076 and GB 1094 standards. These tests verify the transformer's electrical performance and insulation condition before shipment.
03
Third-Party Testing
Support independent testing and certification through recognized organizations such as KEMA and CQC for applicable transformer projects, providing additional verification for project-specific quality and compliance requirements.
04
R&D Innovations in CHBEB Dry Type Transformer Manufacturing
CHBEB dry type transformers incorporate advanced R&D engineering to deliver maximum operational reliability and performance across demanding industrial environments.
Low-Loss Design
CHBEB optimizes magnetic circuit design and uses high-performance silicon steel sheets to improve the efficiency of dry type transformers. These technologies enable no-load losses to be reduced by 15–20% and load losses by 10–15%, helping lower energy consumption during long-term operation.
High Reliability Design
CHBEB develops reinforced winding, insulation, and structural designs to withstand demanding electrical and mechanical conditions. Its dry type transformers have passed short-circuit, overload, and vibration tests, with an annual product failure rate of less than 0.05%, supporting stable and reliable long-term operation.
High-Temperature Tolerance
CHBEB develops optimized winding and insulation systems for stable performance under elevated temperatures. Enhanced thermal design enables dry type transformers to maintain reliable operation at 95°C for 1,000 hours, supporting consistent electrical and insulation performance in high-temperature environments.
Material Innovation
CHBEB applies high-quality silicon steel sheets and advanced insulation materials to improve the electrical, thermal, and mechanical performance of dry type transformers. These material innovations can extend service life by 20–30% and increase efficiency by 5–8%, supporting more durable and energy-efficient operation.
Comprehensive Service Support from CHBEB for Your Transformer Projects
CHBEB provides practical support from technical evaluation and project coordination to delivery and after-sales service.
Technical Support & Free Design Drawings
CHBEB provides technical assistance and drawings to help customers confirm transformer specifications and equipment requirements before production.
Support includes:
• Free technical drawings for project evaluationa
• Transformer specification and selection support
• Electrical and installation requirement consultation
• Product dimension and interface confirmation
• Responsive technical communication
Fast Production & Logistics Support
CHBEB coordinates production and shipment according to project schedules, product requirements, and delivery conditions.
Support includes:
• Standard lead time of 3–6 weeks
• Expedited delivery available within 1 week
• Production scheduling based on project requirements
• Export packaging for transformer transportation
• Shipping and logistics coordination
After-Sales & Lifecycle Support
CHBEB provides technical assistance and warranty coverage to support reliable transformer operation throughout its service life.
After-sales support includes:
• 3-year warranty for complete transformers
• 2-year warranty for spare parts
• Free lifecycle maintenance guidance
• Installation and commissioning guidance
• Technical troubleshooting and operation support
FAQ
Q: What is the MOQ for the 2000 kVA dry type transformer?
A: The MOQ is 1 unit, allowing customers to order a single transformer for project requirements.
Q: Can the 2000 kVA dry type transformer accommodate future increases in electrical demand?
A: The 2000 kVA rating provides additional capacity for planned load growth when the present demand is below the rated limit. Buyers should evaluate projected peak demand, motor starting currents, nonlinear loads, and expected expansion before finalizing the capacity. CHBEB can assess the anticipated load profile to help determine whether this rating meets both current and future requirements.
Q: What information is needed to specify K-13 or K-20 harmonic protection for a 2000 kVA transformer?
A: Buyers should provide the expected harmonic spectrum, nonlinear load types, neutral current requirements, and anticipated loading profile. These details help determine whether a K-13 or K-20 configuration is appropriate. CHBEB can review the electrical requirements and confirm the applicable winding and neutral-conductor design before production.
Q: How can buyers compare the standard 2000 kVA configuration with a project-specific design?
A: Buyers should compare the required voltage ratings, impedance, winding materials, cooling method, enclosure protection, harmonic requirements, and connection arrangements against the standard specification. CHBEB can identify configuration changes needed to meet project drawings, utility requirements, and equipment-interface constraints before order confirmation.
Q: What should buyers confirm before approving the final transformer design?
A: Before design approval, buyers should verify the electrical ratings, vector group, terminal layout, enclosure dimensions, protection interfaces, guaranteed losses, and required test documentation. Confirming these details against the approved single-line diagram and project specifications helps reduce discrepancies during manufacturing, installation, and commissioning.