Key Advantages
This 200 kVA pad-mounted transformer prioritizes energy efficiency and dependable outdoor operation. Its three-phase design ensures smooth voltage regulation and safe service in standard distribution environments.
Product Use
The pad - mounted transformer serves as an integrated prefabricated product that combines distribution network power supply unit cables, high - voltage control, protection, substation, and power distribution equipment. It is widely applied in urban and rural distribution networks. The transformer and high - low voltage equipment are closely connected into one unit. Three sides of the transformer are exposed to the air, ensuring good heat dissipation conditions. Moreover, the transformer can be separated from the high - low voltage equipment housing, facilitating maintenance. Power distribution switchgear is installed on the high and low voltage sides.
Model Description
Taking the ZBW series as an example, the model is represented as ZBW - 12/0.4 - □ - □ - □.
The first part "ZBW" indicates the prefabricated substation.
"12/0.4" represents the rated voltage levels, with 12kV for the high - voltage side and 0.4kV for the low - voltage side.
The subsequent boxes respectively denote the high - voltage measurement of rated voltage (KV), low - voltage measurement of rated voltage (KV), and rated capacity of the transformer (KVA).

Environmental Conditions of Use
Cooling Method: Air Self-Cooling
Operating Environment Requirements:
The outdoor ambient temperature shall not exceed 40°C and shall not be lower than -45°C; the altitude shall not exceed 1,000 meters; the monthly average temperature shall not exceed 30°C; and the annual average temperature shall not exceed 20°C.
At a temperature of 25°C, the relative air humidity shall not exceed 95%, and the monthly average relative humidity shall not exceed 90%.
Horizontal acceleration shall not exceed 0.3g, and vertical acceleration shall not exceed 0.15g.
The installation environment shall be free from obvious pollution, and shall be free of explosive or corrosive gases and dust. Additionally, the installation site shall be free from violent vibration and impact; the equipment must be installed on a cement platform or another flat, solid platform.
Note:
Should there be any other circumstances not covered by these technical specifications, the user shall negotiate with the Company.
Product Advantages
- Compact structure, small size, easy installation.
- Applicable to ring network and terminal power supply, ensuring personal safety.
- Low loss, low noise, excellent performance, and anti-theft box structure.
- Low temperature rise and strong overload capacity.
Product Structure Features
- Transformer and Chambers: The pad-mounted transformer uses the 813 series oil-immersed transformer with a chip-type oil tank (no oil cushion, fully enclosed). High/low-pressure bushings, tap changers, oil level indicators, pressure release valves, oil release valves, etc., are mounted on the high-pressure chamber end plate for easy observation and operation. Its high/low-pressure chambers are separated by steel plates (relatively independent) and integrated into a complete box.
- Components: It is equipped with plug - in fuses, pressure gauges, pressure relief valves, oil level gauges, oil thermometers, load switches, high - voltage cable joints, off - circuit tap changers, ground points, drain valves, and low - voltage switch cabinets, etc.
- Load Switch: It is an oil - immersed, three - phase linkage switch with a spring operating mechanism. It can be operated with load, and its closing speed has nothing to do with the operating force. There are types such as two - station, four - station T type, and four - T position V type to choose from.
Applicable Standards
This product complies with the following standards:
- GB/T 17467-1998 High-Voltage/Low-Voltage Pre-Installed Substations
- DL/T 537-1993 Technical Conditions for Ordering 6-35kV Box-Type Substations
Structure Characteristics
The skeleton structure of the cabinet shell is made of channel steel and angle steel, ensuring high mechanical strength. The shell itself is crafted from aluminum alloy plates, featuring a smooth surface, elegant appearance, and excellent corrosion resistance. The base of the cabinet is elevated above the foundation by 300–600 mm.
All the doors open outwards from the cabinet shell, with an opening angle of more than 90 degrees, and are equipped with positioning devices. Each door is fitted with a handle, a hidden latch, and waterproof, anti-blocking, and anti-rust locks. The cabinets feature a sealed, theft-proof structure. To ensure that the temperature of all electrical equipment does not exceed the maximum allowable temperature during long-term operation (even under normal ambient air temperatures), the cabinets are equipped with both adequate natural ventilation and heat insulation measures.
The cabinets of the prefabricated substation are provided with a dedicated grounding conductor, which is fitted with fixed connection terminals for connecting to the grounding grid (with no fewer than two terminals in total). The grounding terminals utilize copper bolts with a diameter of no less than 12 mm. The grounding conductor is made of a copper strip, with a current density not exceeding 200 A/mm² and a cross-sectional area of no less than 30 mm²-this design ensures that when the maximum short-circuit current flows through the conductor, there is no overheating and no risk to surrounding objects. Additionally, the dynamic and thermal stability of the dedicated grounding conductor must match the grounding method of the high-voltage power distribution equipment.

|
S/N |
Name |
Unit |
Technical Parameter |
|
1 |
Rated Voltage |
KV |
10/0.4 |
|
2 |
High-voltage Side Rated Voltage |
KV |
10 |
|
3 |
Low-voltage Side Rated Voltage |
KV |
0.4 |
|
4 |
Maximum operating voltage (High voltage side) |
KV |
12 |
|
5 |
Rated Frequency |
Hz |
50 |
|
6 |
Rated Capacity |
KVA |
150-1600 |
|
7 |
High-voltage Switch Heat Stable Capacity |
KA |
20/26 |
|
8 |
Low-voltage Main Circuit Breaker Rated Short-circuit Breaking Capacity |
KA |
35 |
|
9 |
Low-voltage Distribution Circuit Breaker Rated Short-circuit Breaking Capacity |
KA |
35 |
|
10 |
High-voltage Load Switch Transfer Current |
A |
>1500 |
|
11 |
1 min Power Frequency Withstand Voltage |
KV |
35 |
|
12 |
Lightning Impulse Voltage |
KV |
75 |
|
13 |
Cooling Mode |
- |
Oil immersed self-cooling |
|
14 |
High-voltage Backup Fuse Breaking Current |
KA |
50 |
|
15 |
Breaking Current of Plug-in Fuse |
KA |
2.5 |
|
16 |
Ambient Temperature |
℃ |
-35 ~ +40 |
|
17 |
Coil Allowable Temperature Rise |
K |
65 |
|
18 |
No-load Voltage Regulation |
% |
±5% or ±2 × 2.5% |
|
19 |
Noise Level |
dB |
<50 |
|
20 |
Protection Grade of Box Shell |
- |
Not less than IP3X |
Basic Construction Requirements
1. Basic load-bearing requirement: The foundation must withstand a pressure of over 100 kPa.
2. Foundation for elevated areas: Ensure proper drainage around the foundation. The foundation should be constructed with red bricks and cement mortar; the external walls shall be plastered with 1:2 cement mortar (20 mm thick), with 3% waterproofing agent added.
3. Cable chamber drainage: The bottom surface of the cable chamber shall be slightly inclined toward the water collection pipe to facilitate drainage.
4. Steel mesh and rib installation: Use a 150×300 steel mesh with (10×20) diamond-shaped openings; weld ribs to the inner wall of the outer frame.
5. Compliance with standards: Foundation construction shall comply with the relevant provisions of JGJ16-83 Code for Electrical Design of Buildings.
6. Grounding system requirements: Conduct routine inspections on the main grounding steel and its connecting ends. The grounding wire led from the cable trench can be routed along the perimeter of the ring network cabinet or extended from one side for grounding. The grounding resistance shall be ≤ 4 ohms.
7. Dimension reference: Follow the dimensions specified in the construction drawing (as recommended).
8. Cable well flexibility: For user convenience, cable wells can be installed in 3 to 4 directions on-site based on actual conditions.
Product Parameters
|
S/N |
Name |
Unit |
Technical Parameter |
|
1 |
Rated Voltage |
KV |
10/0.4 |
|
2 |
High-voltage Side Rated Voltage |
KV |
10 |
|
3 |
Low-voltage Side Rated Voltage |
KV |
0.4 |
|
4 |
Maximum operating voltage (High voltage side) |
KV |
12 |
|
5 |
Rated Frequency |
Hz |
50 |
|
6 |
Rated Capacity |
KVA |
150-1600 |
|
7 |
High-voltage Switch Heat Stable Capacity |
KA |
20/26 |
|
8 |
Low-voltage Main Circuit Breaker Rated Short-circuit Breaking Capacity |
KA |
35 |
|
9 |
Low-voltage Distribution Circuit Breaker Rated Short-circuit Breaking Capacity |
KA |
35 |
|
10 |
High-voltage Load Switch Transfer Current |
A |
>1500 |
|
11 |
1 min Power Frequency Withstand Voltage |
KV |
35 |
|
12 |
Lightning Impulse Voltage |
KV |
75 |
|
13 |
Cooling Mode |
- |
Oil immersed self-cooling |
|
14 |
High-voltage Backup Fuse Breaking Current |
KA |
50 |
|
15 |
Breaking Current of Plug-in Fuse |
KA |
2.5 |
|
16 |
Ambient Temperature |
℃ |
-35 ~ +40 |
|
17 |
Coil Allowable Temperature Rise |
K |
65 |
|
18 |
No-load Voltage Regulation |
% |
±5% or ±2 × 2.5% |
|
19 |
Noise Level |
dB |
<50 |
|
20 |
Protection Grade of Box Shell |
- |
Not less than IP3X |
Insulation Level
|
Rated voltage(KV) |
10 |
0.4 |
||
|
Transformer |
Switch to ground and phase to phase |
Between disconnectors |
||
|
Power frequency withstand voltage (KV) |
35 |
42 |
48 |
2.5 |
|
Peak value of impulse withstand voltage(KV) |
75 |
75 |
85 |
– |
Transformer
Selected new S9 series transformer body, low loss, good overload capacity, strong short-circuit resistance, all fasteners are protected. The S11 series ring jointless core transformer with better performance can also be selected.
|
Capacity KVA |
Voltage KV |
Join group label |
No-load current % |
No load loss W |
Impedance voltage % |
Load loss |
|||||
|
High tension |
Low pressure |
S9 |
S10 |
S11 |
S9 |
S10 |
S11 |
||||
|
160 |
10±5% or 2×2.5% |
0.4 |
Dyn11 Yno |
1.4 |
1.4 |
0.2 |
400 |
320 |
255 |
4.0 |
2200 |
|
200 |
1.3 |
1.3 |
0.2 |
480 |
380 |
305 |
2600 |
||||
|
250 |
1.2 |
1.2 |
0.2 |
560 |
450 |
360 |
3050 |
||||
|
315 |
1.1 |
1.1 |
0.2 |
670 |
530 |
425 |
3650 |
||||
|
400 |
1.0 |
1.0 |
0.15 |
800 |
650 |
505 |
4300 |
||||
|
500 |
1.0 |
1.0 |
0.15 |
960 |
750 |
605 |
5100 |
||||
|
630 |
0.9 |
0.9 |
0.15 |
1200 |
910 |
755 |
6200 |
||||
|
800 |
0.8 |
0.8 |
0.15 |
1400 |
1080 |
980 |
7500 |
||||
|
1000 |
0.7 |
0.7 |
- |
1700 |
1260 |
- |
4.5 |
10300 |
|||
|
1250 |
0.6 |
0.6 |
- |
1950 |
- |
- |
12000 |
||||
|
Item Name |
Units |
315A |
630A |
|
|
Rated voltage |
KV |
12 |
12 |
|
|
Maximum current |
A |
315 |
630 |
|
|
Rated frequency |
Hz |
50 |
50 |
|
|
Rated short-circuit closing current |
kA |
31.5 |
50 |
|
|
Rated short-time withstand current |
kA |
12.5 |
50 |
|
|
Rated short endurance time |
S |
2 |
2 |
|
|
Mechanical life |
Second-rate |
2000 |
2000 |
|
|
Lightning impulse test |
Phase to phase |
KV |
75 |
75 |
|
Isolation fracture |
85 |
85 |
||
|
1min power frequency withstand voltage |
Phase to phase |
KA |
42 |
42 |
|
Isolation fracture |
48 |
48 |
||
|
Rated peak withstand current |
KV |
31.5 |
50 |
|
|
Capacity |
A |
B |
C |
H |
Weight KG |
|
200kVA and below |
1830 |
1420 |
820 |
1850 |
< 2800 |
|
250-400kVA |
1830 |
1450 |
850 |
1980 |
3000-3300 |
|
500-630kVA |
1830 |
1480 |
880 |
2070 |
3600-3950 |
|
800kVA |
2200 |
1700 |
950 |
2170 |
4500 |
Note:The above is the standard size for reference.
|
Capacity |
A |
B |
C |
H |
Weight KG |
|
315kVA |
2560 |
1600 |
600 |
1000 |
3050 |
|
400kVA |
2560 |
1600 |
600 |
1000 |
3270 |
|
500kVA |
2560 |
1600 |
600 |
1000 |
3400 |
|
630kVA |
2560 |
1600 |
600 |
1000 |
3900 |
|
800kVA |
2760 |
1600 |
800 |
1000 |
4200 |
|
1000kVA |
2760 |
1950 |
800 |
1000 |
4800 |
|
1250kVA |
2910 |
1950 |
800 |
1000 |
5400 |
|
1600kVA |
2200 |
1700 |
950 |
2170 |
4500 |
Note:The above is the standard size for reference.
Outline Mounting Dimension(mm)




Mounting Dimension(mm)

Detailed Views






Packing and Shipping



Customer Factory Inspection






Hot Tags: 200 kva pad mount three-phase oil-immersed distribution transformer, China 200 kva pad mount three-phase oil-immersed distribution transformer manufacturers, suppliers, factory, 2500 KVA Pad Mount Three-Phase Oil-Immersed Distribution Transformer, 167 kva pad mount transformer, 5000 KVA Pad Mount Three-Phase Oil-Immersed Distribution Transformer, Single Phase Pad Mounted Transformer (URD Series), 1000 KVA Pad Mount Three-Phase Oil-Immersed Distribution Transformer, 25 kva pad mount transformer