The 1 MVA Milestone: Robustness & Reliability
The 1000 kVA Dry Type Transformer represents the "gold standard" capacity for main building power and heavy industrial feeders. It marks the transition into the megawatt class, where the physical stresses on the windings require advanced structural engineering.
As a high-capacity three phase dry type transformer, this unit must physically withstand the "magnetic hammer" effect of a short circuit. To guarantee this, we utilize a Heavy-Duty Channel Steel Framework. Unlike smaller units that rely on simple tie-rods, this 1 MVA model uses upper and lower steel crossbeams to clamp the coils like a vice. This rigidity prevents the windings from telescoping or shifting during electrical faults, preventing catastrophic mechanical failure.
Cast Resin Technology: The Silica Ratio
The longevity of a 1000 kVA unit depends entirely on the quality of its insulation mixture. We utilize a premium dry type cast resin system that functions more like engineered stone than plastic.
- The Mixture: We mix epoxy resin with a high concentration of Quartz Silica Flour under vacuum. This isn't just for insulation; the silica adds massive mechanical strength.
- Crack Prevention: Because this mixture is tuned to have the same thermal elongation properties as the copper conductor, the insulation moves with the metal, not against it. This means the coil remains solid and crack-free, even when the unit undergoes rapid heating from a cold start (-25°C) to full operating load.
Brass tap changer links on 1000 kVA cast resin transformer coil
surface.
Partial Discharge & Electrical Health
For a 10 kV or 11 kV transformer dry type insulation system, "Partial Discharge" (PD) is the silent indicator of insulation failure.
- The Standard: While industry standards often allow for up to 20pC (pico-Coulombs) of discharge, our 1000 kVA coils are cast under strict vacuum conditions to prevent air voids.
- The Result: We guarantee a Partial Discharge level of <10 pC. This exceptionally low value indicates a void-free solid insulation, ensuring the dielectric material is not slowly eroding from the inside out, which is critical for high-reliability assets like hospital mains or data center feeds.
Factory partial discharge testing in shielded room ensuring
low PD levels.
Technical Data Sheet
|
Technical Parameter |
Specification Data |
|
Rated Power |
1000 kVA (1 MVA) |
|
Primary Voltage |
6kV / 10kV / 11kV / 13.8kV |
|
Secondary Voltage |
400V / 415V / 480V |
|
Insulation Tech |
Vacuum Cast Resin (Quartz Filled) |
|
Partial Discharge |
< 10 pC (High reliability) |
|
Impedance Voltage |
6.0% (Standard) |
|
Cooling |
AN (Natural) / AF (Forced +40%) |
|
Enclosure Rating |
IP20 / IP23 / IP33 (Dust/Splash Proof) |
|
Temperature Sensor |
PT100 in LV Windings |
Typical Application Context
- Public Infrastructure: Powering metro stations or airport terminals where the low smoke (F1) and non-explosive nature of the resin is mandatory for passenger safety.
- Industrial Plants: Installed in "dirty" manufacturing environments (e.g., cement or textile mills). The solid resin surface is smooth and non-tracking, allowing conductive dust to be easily wiped off during maintenance shutdowns.
- Indoor Substations: Replacing oil units in basement switchrooms to remove the fire risk and the need for expensive oil-catchment civil works.
1000 kVA dry type transformer installed in a public metro station
substation.